Title: ПРО «ПЛАВАЮЧІ» ОПОРНІ ІНТЕРВАЛИ ПРИ ВИЗНАЧЕННІ ФАЗИ З ВИТОКОМ
Other Titles: О "плавающих" опорных интервалах при определении фазы с утечкой
About "Floated" Reference Intervals during Detection the Phase with Leak
Authors: КОВАЛЬОВ, О.П.
КОВАЛЕВ, А.П.
KOVALIOV, O.
ЧОРНОУС, Є.В.
ЧОРНОУС, Е.В.
CHORNOUS, Ye.
Keywords: пристрій визначення пошкодженої фази
опорні фазові інтервали
опір витоку
аргумент потенціалу нейтралі
опір ізоляціі
перехідний процес
несиметрія мережі
вищі гармоніки
високоомний витік
устройство определения поврежденной фазы
опорные фазовые интервалы
сопротивление утечки
аргумент потенциала нейтрали
сопротивление изоляции
переходный процесс
несимметрия сети
высшие гармоники
высокоомная утечка
fault phase detection device
the phase reference intervals
leakage resistance
the argument of potential neutral
insulation resistance
transient
asymmetry in the network
the higher harmonics
high-resistance leak
Issue Date: 2013
Publisher: ДонНТУ
Citation: Наукові праці Донецького національного технічного університету. Серія "Електротехніка і енергетика". № 2 (15), 2013 р., 338 с.
Series/Report no.: Электротехника и энергетика;
Abstract: Обгрунтована можливість підвищення стійкості до завад і спотворень пристрою визначення пошкодженої фази в мережі з ізольованою нейтраллю шляхом зміщення опорних фазових інтервалів в функції опору витоку або амплітуди потенціалу нейтралі. Встановлено функціональний зв'язок між опором витоку, амплітудою потенціалу нейтралі і його аргументом з урахуванням впливу поперечної несиметріі в мережі.
Description: The aim of this investigation is to improve the reliability and acceleration of the faulted phase detection device in electric networks with the isolated neutral. Survey mythology presents the simulation mode of electric transmission network with a single-phase leakage with the asymmetry of the insulation network, which is inserted through the asymmetry factor. The obtained dependence of the neutral potential argument on its amplitude with the transverse asymmetry indicates that the errors in the determination of this argument may be insignificant. Moreover they reveal themselves only with l1igh-resistance leak, allowing approximate the expression for the displacement of the "floating" reference intervals for leakage in any phase of a simple linear function. There is an example of the device work of the faulted phase detection. It refers to the results of mathematical simulation mode of electric network with leakage, where have been the worst testing conditions (distortion and interference of the electric network), namely, a large leakage resistance and as a result, protracted transient, unfavorable phase switching, presence of a third harmomc component in the neutral potential. The digital model of the determination faulted phase device clearly demonstrates the expediency of the reference phase shift intervals. Thus, it demonstrates the possibility of increasing resistance to distortion and interference of the device faulty phase detection by shifting the reference phase intervals in functions of leakage resistance or potential amplitude neutral.