Please use this identifier to cite or link to this item: http://ea.donntu.edu.ua:8080/jspui/handle/123456789/22567
Title: ОБҐРУНТУВАННЯ СПОСОБУ ЗАХИСНОГО ЗНЕСТРУМЛЕННЯ МІСЦЯ ВИНИКНЕННЯ МІЖФАЗНОГО ДУГОУТВОРЕННЯ В МЕРЕЖІ ЖИВЛЕННЯ АСИНХРОННОГО ДВИГУНА
Other Titles: Justification of the Method of Power Supply Disconnection of Phase to Phase Electrical Arcing in the Power Network of the Induction Motor
Обоснование способа защитного обесточивания места возникновения междуфазного дугообразования в сети питания асинхронного двигателя
Authors: Ковальова, І.В.
Kovalyova, I.
Ковалёва, И.В.
Keywords: міжфазне дугоутворення
асинхронний двигун
двобічне знеструмлення
апарат захисту
заземлююча жила
ізоляція
междуфазное дугообразование
асинхронный двигатель
двустороннее обесточивание
аппарат защиты
заземляющая жила
изоляция
phase to phase electric arcing
induction motor
two-end power supply disconnection
protection device
ground wire
insulation
Issue Date: 2013
Publisher: Донецький національний технічний університет
Citation: Наукові праці Донецького національного технічного університету. Серія: Обчислювальна техніка та автоматизація. Випуск 1 (24). - Донецьк, ДонНТУ, 2013. С - 19-24
Abstract: Досліджена комп’ютерна модель процесу міжфазного дугоутворення в мережі живлення асинхронного двигуна і отримані закономірності зміни величини струму його статора з урахуванням параметрів живлячого кабелю та відстані до місця ушкодження. Обґрунтовано спосіб визначення стану міжфазного дугоутворення з подальшим швидкодіючим двобічним знеструмленням аварійної точки силового приєднання.
Description: Operating conditions of electromechanical equipment of mine technological section is determined by its location nonstationarity, which, in turn, makes it necessary to use of flexible cables. Phase to phase electrical arcing is the specifically view of emergency conditions in power supply of the mine section electrotechnical complex, occurs as a result of insulation damage of internal power wires by bare ground wire with increased external compression of the cable, that is determined by complex operating conditions the cable network. In this case, the resistance of an electric arc maybe comparable with the load resistance and arcing process will not be detected by overcurrent protection means. We studied computer models of the process of phase to phase electrical arcing in the power network of the induction motor and obtained the laws of the value of its stator current taking into account the parameters of the feeder cable and the distance to the fault location. We considered the way of defining the state of phase to phase electrical arcing with further fast disconnection of emergency point of power connection, which is based on determining the difference of the linear currents in three-phase induction motor stator circuit emergency network with followed disconnection of the three-phase circuits and connection one of the phase windings of the induction motor stator to its normally earthed body through the resistor. This provides a quick acting two-end power supply disconnection emergency conditions in power supply of the mine section electrotechnical complex.
URI: http://ea.donntu.edu.ua/handle/123456789/22567
ISSN: 2075-4272
Appears in Collections:Випуск 1 (24)'2013
Статті кафедри ГЕА

Files in This Item:
File Description SizeFormat 
ковалева.pdf520,18 kBAdobe PDFView/Open


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.