Please use this identifier to cite or link to this item: http://ea.donntu.edu.ua:8080/jspui/handle/123456789/23504
Title: МОДЕЛЮВАННЯ ТА АНАЛІЗ ВПЛИВУ ТИРИСТОРНИХ УСТАНОВОК ПОЗДОВЖНЬОЇ КОМПЕНСАЦІЇ НА ЯКІСТЬ РОБОТИ ЕЛЕКТРОЕНЕРГЕТИЧНИХ СИСТЕМ
Other Titles: Моделирование и анализ влияния тиристорных установок продольной компенсации на качество работы электроэнергетических систем
Modeling and Analysis of the Impact of aThyristor Controlled Series Capacitor at Power System Quality
Authors: ЯНДУЛЬСЬКИЙ, О.С.
МАЦЕЙКО, В.В.
ЯНДУЛЬСКИЙ, А.С.
МАЦЕЙКО, В.В.
YANDULSKYY, O.
MATSEYKO, V.
Keywords: гнучкі системи передачі змінним струмом
статичний тиристорний компенсатор
тиристорна установка поздовжньої компенсації
система керування
моделювання
гибкие системы передачи переменного тока
статический тиристорный компенсатор
тиристорная установка продольной компенсации
система управления
flexible alternative current transmission systems
static var compensator
thyristor controlled series capacitor
control system
Issue Date: 2013
Publisher: ДонНТУ
Citation: Наукові праці Донецького національного технічного університету. Серія "Електротехніка і енергетика". № 2 (15), 2013 р., 338 с.
Series/Report no.: Электротехника и энергетика;
Abstract: Розглянута необхідність інтеграції систем гнучкої передачі змінним струмом в ОЕС України. Проаналізовано світовий досвід впровадження гнучких передач змінним струмом та їхні функціональні можливості. Розроблена автоматична система керування тиристорною установкою поздовжньої компенсації та проведений аналіз впливу тиристорних установок поздовжньої компенсації на підвищення пропускної здатності ліній електропередач
Description: Flexible AC transmission systems (FACTS) controllers have been mainly used for solving various power system steady state control problems. The world’s literature shows an increasing interest in this subject for the last two decades, where the enhancement of system stability using FACTS controllers has been extensively investigated. Some of the utility experience, real-world installations, and semiconductor technology development have been reviewed and summarized. TCSC devices are used to improve real power and eliminate line loses in ac systems. An additional task of TCSC is to increase transmission capacity as result of power oscillation damping. The control scheme of a typical TCSC is described. A typical TCSC module consists of a fixed series capacitor in parallel with a thyristor controlled reactor. In a TCSC, two main operational blocks can be clearly identified, i.e. an external control and an internal control. The function of the external control is to operate the controller to accomplish specified compensation objectives; this control directly relies on measured systems variables to define the reference for the internal control, which is usually the value of the controller reactance. The function of the internal control is to provide appropriate gate drive signals for the thyristor valve to produce the desired compensating reactance. Line active power, line reactive power, line current magnitude and bus voltage magnitudes are all candidates to be considered in the selection of input signals for the TCSC stability control loop. Of these possible input signals, active power and current are the most commonly discussed in the literature. That’s why active power is used as an input signal of a controller. The results of applying the proposed TCSC controller design for optimal power flow and increase the system damping for low frequency oscillations are analyzed
URI: http://ea.donntu.edu.ua/handle/123456789/23504
Appears in Collections:2013_Випуск № 2 (15)

Files in This Item:
File Description SizeFormat 
299_2.pdf386,07 kBAdobe PDFView/Open


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.